Lorem ipsum dolor amet, consectetuer adipiscing elit. Aenean commodo ligula eget dolor massa. Cum sociis natoque penatibus et magnis dis parturient montes, nascetur ridiculus mus.

Baker

Follow Us:

Installing Continental Control Systems Accu CTs

Installing Continental Control Systems Accu CTs

You are here:
< Back

Like most solid core ferrite CTs, Accu CTs from Continental Control Systems (CCS) are prone to damage if dropped, struck, or closed aggressively. In order to avoid damage during installation, the CT should not be forced closed. This can cause chips or cracks in the ferrite core, which reduces the accuracy of the CT.

To prevent damage to CCS CTs, the tabs on either side of the hinged portion of the CT should be squeezed together. The CT can then be closed as normal. The image below shows the tabs. When the tabs are squeezed, the CT should close without applying significant pressure. Failure to follow this step can cause damage to the CT. This damage may not be readily visible.

CT tabs with light pressure applied (under the thumb and index finger)